9 Grid Strength and Fault Levels

A transmission line is primarily copper and can be modeled as a resistor.  Transformers are coils of wire and hence have inductance. Therefore, a transmission system can be represented by an impedance ZT = R + jXL where R is the resistance and XL is the inductive reactance.  Ideally, utilities want to keep R and XL small to minimize losses in transmission.

Fault level is defined to be maximum voltage times the short circuit current.  For example, if a system has a 230 kV rating and a resistance of 10 Ohms, the short circuit current would be I = V/R = 230 kV/ 10 Ohms = 23 kA so the fault level is 23 kA*230 kV = 5.29 GVA.   An acceptable voltage drop is roughly 5%.  Hence, loads totaling up to 0.05*5.29 GVA = 264.5 MVA could be connected. (Lynn, 171)

Works Cited
Lynn, Paul A. Electricity from Wave and Tide : An Introduction to Marine Energy. Wiley, 2014.

License

Icon for the Creative Commons Attribution 4.0 International License

Smart Grids Copyright © by Jim Trepka is licensed under a Creative Commons Attribution 4.0 International License, except where otherwise noted.

Share This Book